Vendor CVEs
Hitachienergy
All CVEs
105 total · sorted by risk| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2019-5620 | Cri | 0.72 | 9.8 | 0.70 | Apr 29, 2020 | ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function. | ||
| CVE-2024-2013 | Cri | 0.65 | 10.0 | 0.01 | Jun 11, 2024 | An authentication bypass vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway component that if exploited allows attackers without any access to interact with the services and the post-authentication attack surface. | ||
| CVE-2019-18253 | Cri | 0.65 | 10.0 | 0.02 | Nov 27, 2019 | An attacker could use specially crafted paths in a specific request to read or delete files from Relion 670 Series (versions 1p1r26, 1.2.3.17, 2.0.0.10, RES670 2.0.0.4, 2.1.0.1, and prior) outside the intended directory. | ||
| CVE-2024-4872 | Cri | 0.64 | 9.9 | 0.01 | Aug 27, 2024 | A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential. | ||
| CVE-2024-3980 | Cri | 0.64 | 9.9 | 0.01 | Aug 27, 2024 | The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the… | ||
| CVE-2022-3682 | Cri | 0.64 | 9.9 | 0.01 | Mar 28, 2023 | A vulnerability exists in the SDM600 file permission validation. An attacker could exploit the vulnerability by gaining access to the system and uploading a specially crafted message to the system node, which could result in Arbitrary code Executing. This issue affects: All… | ||
| CVE-2018-14805 | Cri | 0.64 | 9.8 | 0.05 | Aug 29, 2018 | ABB eSOMS version 6.0.2 may allow unauthorized access to the system when LDAP is set to allow anonymous authentication, and specific key values within the eSOMS web.config file are present. Both conditions are required to exploit this vulnerability. | ||
| CVE-2024-2012 | Cri | 0.59 | 9.1 | 0.01 | Jun 11, 2024 | vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway that if exploited an attacker could use to allow unintended commands or code to be executed on the UNEM server allowing sensitive data to be read or modified or could cause other unintended behavior | ||
| CVE-2021-40333 | Cri | 0.59 | 9.0 | 0.01 | Dec 2, 2021 | Weak Password Requirements vulnerability in Hitachi Energy FOX61x, XCM20 allows an attacker to gain unauthorized access to the Data Communication Network (DCN) routing configuration. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions… | ||
| CVE-2022-3388 | Hig | 0.57 | 8.8 | 0.00 | Nov 21, 2022 | An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. | ||
| CVE-2017-16731 | Hig | 0.57 | 8.8 | 0.01 | Dec 20, 2017 | An Unprotected Transport of Credentials issue was discovered in ABB Ellipse 8.3 through Ellipse 8.9 released prior to December 2017 (including Ellipse Select). A vulnerability exists in the authentication of Ellipse to LDAP/AD using the LDAP protocol. An attacker could exploit… | ||
| CVE-2024-2011 | Hig | 0.56 | 8.6 | 0.00 | Jun 11, 2024 | A heap-based buffer overflow vulnerability exists in the FOXMAN-UN/UNEM that if exploited will generally lead to a denial of service but can be used to execute arbitrary code, which is usually outside the scope of a program's implicit security policy | ||
| CVE-2021-40334 | Hig | 0.56 | 8.6 | 0.01 | Dec 2, 2021 | Missing Handler vulnerability in the proprietary management protocol (port TCP 5558) of Hitachi Energy FOX61x, XCM20 allows an attacker that exploits the vulnerability by activating SSH on port TCP 5558 to cause disruption to the NMS and NE communication. This issue affects:… | ||
| CVE-2022-29490 | Hig | 0.55 | 8.5 | 0.01 | Sep 12, 2022 | Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X… | ||
| CVE-2024-7940 | Hig | 0.54 | 8.3 | 0.01 | Aug 27, 2024 | The product exposes a service that is intended for local only to all network interfaces without any authentication. | ||
| CVE-2022-3929 | Hig | 0.54 | 8.3 | 0.00 | Jan 5, 2023 | Communication between the client and the server application of the affected products is partially done using CORBA (Common Object Request Broker Architecture) over TCP/IP. This protocol is not encrypted and allows tracing of internal messages. This issue affects * … | ||
| CVE-2026-2460 | Hig | 0.53 | 8.1 | 0.00 | Feb 24, 2026 | A vulnerability exists in REB500 for an authenticated user with low-level privileges to access and alter the content of directories by using the DAC protocol that the user is not authorized to do so. | ||
| CVE-2026-2459 | Hig | 0.53 | 8.1 | 0.00 | Feb 24, 2026 | A vulnerability exists in REB500 for an authenticated user with Installer role to access and alter the contents of directories that the role is not authorized to do so. | ||
| CVE-2024-3982 | Hig | 0.53 | 8.2 | 0.00 | Aug 27, 2024 | An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level is not enabled and only users… | ||
| CVE-2021-35535 | Hig | 0.53 | 8.1 | 0.01 | Nov 18, 2021 | Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during… | ||
| CVE-2024-28020 | Hig | 0.52 | 8.0 | 0.00 | Jun 11, 2024 | A user/password reuse vulnerability exists in the FOXMAN-UN/UNEM application and server management. If exploited a malicious high-privileged user could use the passwords and login information through complex routines to extend access on the server and other services. | ||
| CVE-2024-2378 | Hig | 0.52 | 8.0 | 0.00 | Apr 30, 2024 | A vulnerability exists in the web-authentication component of the SDM600. If exploited an attacker could escalate privileges on af-fected installations. | ||
| CVE-2022-3927 | Hig | 0.52 | 8.0 | 0.01 | Jan 5, 2023 | The affected products store both public and private key that are used to sign and protect Custom Parameter Set (CPS) file from modification. An attacker that manages to exploit this vulnerability will be able to change the CPS file, sign it so that it is trusted as the… | ||
| CVE-2018-1168 | Hig | 0.51 | 7.8 | 0.00 | Feb 21, 2018 | This vulnerability allows local attackers to escalate privileges on vulnerable installations of ABB MicroSCADA 9.3 with FP 1-2-3. An attacker must first obtain the ability to execute low-privileged code on the target system in order to exploit this vulnerability. The specific… | ||
| CVE-2022-3683 | Hig | 0.50 | 7.7 | 0.00 | Mar 28, 2023 | A vulnerability exists in the SDM600 API web services authorization validation implementation. An attacker who successfully exploits the vulnerability could read data directly from a data store that is not restricted, or insufficiently protected, having access to sensitive… | ||
| CVE-2021-35529 | Hig | 0.50 | 7.7 | 0.01 | Aug 20, 2021 | Insufficiently Protected Credentials vulnerability in client environment of Hitachi ABB Power Grids Retail Operations and Counterparty Settlement Billing (CSB) allows an attacker or unauthorized user to access database credentials, shut down the product and access or alter. This… | ||
| CVE-2026-1773 | Hig | 0.49 | 7.5 | 0.00 | Feb 24, 2026 | IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the… | ||
| CVE-2024-2377 | Hig | 0.49 | 7.6 | 0.00 | Apr 30, 2024 | A vulnerability exists in the too permissive HTTP response header web server settings of the SDM600. An attacker can take advantage of this and possibly carry out privileged actions and access sensitive information. | ||
| CVE-2022-2081 | Hig | 0.49 | 7.5 | 0.01 | Jan 4, 2024 | A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the… | ||
| CVE-2022-4608 | Hig | 0.49 | 7.5 | 0.01 | Jul 26, 2023 | A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500… | ||
| CVE-2022-2502 | Hig | 0.49 | 7.5 | 0.01 | Jul 26, 2023 | A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced… | ||
| CVE-2022-3685 | Hig | 0.49 | 7.5 | 0.00 | Mar 28, 2023 | A vulnerability exists in the SDM600 software. The software operates at a privilege level that is higher than the minimum level required. An attacker who successfully exploits this vulnerability can escalate privileges. This issue affects: All SDM600 versions prior to… | ||
| CVE-2022-3684 | Hig | 0.49 | 7.5 | 0.01 | Mar 28, 2023 | A vulnerability exists in a SDM600 endpoint. An attacker could exploit this vulnerability by running multiple parallel requests, the SDM600 web services become busy rendering the application unresponsive. This issue affects: All SDM600 versions prior to version 1.2 FP3 HF4… | ||
| CVE-2022-2277 | Hig | 0.49 | 7.5 | 0.01 | Sep 14, 2022 | Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future… | ||
| CVE-2022-29922 | Hig | 0.49 | 7.5 | 0.01 | Sep 14, 2022 | Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a… | ||
| CVE-2022-1778 | Hig | 0.49 | 7.5 | 0.00 | Sep 14, 2022 | Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue… | ||
| CVE-2022-28613 | Hig | 0.49 | 7.5 | 0.01 | May 2, 2022 | A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500… | ||
| CVE-2021-35533 | Hig | 0.49 | 7.5 | 0.01 | Nov 26, 2021 | Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a… | ||
| CVE-2021-35527 | Hig | 0.49 | 7.5 | 0.01 | Jul 14, 2021 | Password autocomplete vulnerability in the web application password field of Hitachi ABB Power Grids eSOMS allows attacker to gain access to user credentials that are stored by the browser. This issue affects: Hitachi ABB Power Grids eSOMS version 6.3 and prior versions. | ||
| CVE-2021-27196 | Hig | 0.49 | 7.5 | 0.02 | Jun 14, 2021 | Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of… | ||
| CVE-2021-26845 | Hig | 0.49 | 7.5 | 0.01 | Jun 14, 2021 | Information Exposure vulnerability in Hitachi ABB Power Grids eSOMS allows unauthorized user to gain access to report data if the URL used to access the report is discovered. This issue affects: Hitachi ABB Power Grids eSOMS 6.0 versions prior to 6.0.4.2.2; 6.1 versions prior to… | ||
| CVE-2019-19094 | Hig | 0.49 | 7.6 | 0.01 | Apr 2, 2020 | Lack of input checks for SQL queries in ABB eSOMS versions 3.9 to 6.0.3 might allow an attacker SQL injection attacks against the backend database. | ||
| CVE-2019-18247 | Hig | 0.49 | 7.5 | 0.02 | Nov 27, 2019 | An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service. | ||
| CVE-2018-20720 | Hig | 0.49 | 7.5 | 0.02 | Jan 16, 2019 | ABB Relion 630 devices 1.1 before 1.1.0.C0, 1.2 before 1.2.0.B3, and 1.3 before 1.3.0.A6 allow remote attackers to cause a denial of service (reboot) via a reboot command in an SPA message. | ||
| CVE-2025-2500 | Hig | 0.48 | 7.4 | 0.00 | May 30, 2025 | A vulnerability exists in the SOAP Web services of the Asset Suite versions listed below. If successfully exploited, an attacker could gain unauthorized access to the product and the time window of a possible password attack could be expanded. | ||
| CVE-2024-28021 | Hig | 0.48 | 7.4 | 0.00 | Jun 11, 2024 | A vulnerability exists in the FOXMAN-UN/UNEM server that affects the message queueing mechanism’s certificate validation. If exploited an attacker could spoof a trusted entity causing a loss of confidentiality and integrity. | ||
| CVE-2023-1514 | Hig | 0.48 | 7.4 | 0.00 | Dec 19, 2023 | A vulnerability exists in the component RTU500 Scripting interface. When a client connects to a server using TLS, the server presents a certificate. This certificate links a public key to the identity of the service and is signed by a Certification Authority (CA), allowing the… | ||
| CVE-2025-39202 | Hig | 0.47 | 7.3 | 0.00 | Jun 24, 2025 | A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption. | ||
| CVE-2024-41153 | Hig | 0.47 | 7.2 | 0.02 | Oct 29, 2024 | Command injection vulnerability in the Edge Computing UI for the TRO600 series radios that allows for the execution of arbitrary system commands. If exploited, an attacker with write access to the web UI can execute commands on the device with root privileges, far more extensive… | ||
| CVE-2021-35534 | Hig | 0.47 | 7.2 | 0.02 | Nov 18, 2021 | Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to… |
- risk 0.72cvss 9.8epss 0.70
ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function.
- risk 0.65cvss 10.0epss 0.01
An authentication bypass vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway component that if exploited allows attackers without any access to interact with the services and the post-authentication attack surface.
- risk 0.65cvss 10.0epss 0.02
An attacker could use specially crafted paths in a specific request to read or delete files from Relion 670 Series (versions 1p1r26, 1.2.3.17, 2.0.0.10, RES670 2.0.0.4, 2.1.0.1, and prior) outside the intended directory.
- risk 0.64cvss 9.9epss 0.01
A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential.
- risk 0.64cvss 9.9epss 0.01
The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the…
- risk 0.64cvss 9.9epss 0.01
A vulnerability exists in the SDM600 file permission validation. An attacker could exploit the vulnerability by gaining access to the system and uploading a specially crafted message to the system node, which could result in Arbitrary code Executing. This issue affects: All…
- risk 0.64cvss 9.8epss 0.05
ABB eSOMS version 6.0.2 may allow unauthorized access to the system when LDAP is set to allow anonymous authentication, and specific key values within the eSOMS web.config file are present. Both conditions are required to exploit this vulnerability.
- risk 0.59cvss 9.1epss 0.01
vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway that if exploited an attacker could use to allow unintended commands or code to be executed on the UNEM server allowing sensitive data to be read or modified or could cause other unintended behavior
- risk 0.59cvss 9.0epss 0.01
Weak Password Requirements vulnerability in Hitachi Energy FOX61x, XCM20 allows an attacker to gain unauthorized access to the Data Communication Network (DCN) routing configuration. This issue affects: Hitachi Energy FOX61x versions prior to R15A. Hitachi Energy XCM20 versions…
- risk 0.57cvss 8.8epss 0.00
An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role.
- risk 0.57cvss 8.8epss 0.01
An Unprotected Transport of Credentials issue was discovered in ABB Ellipse 8.3 through Ellipse 8.9 released prior to December 2017 (including Ellipse Select). A vulnerability exists in the authentication of Ellipse to LDAP/AD using the LDAP protocol. An attacker could exploit…
- risk 0.56cvss 8.6epss 0.00
A heap-based buffer overflow vulnerability exists in the FOXMAN-UN/UNEM that if exploited will generally lead to a denial of service but can be used to execute arbitrary code, which is usually outside the scope of a program's implicit security policy
- risk 0.56cvss 8.6epss 0.01
Missing Handler vulnerability in the proprietary management protocol (port TCP 5558) of Hitachi Energy FOX61x, XCM20 allows an attacker that exploits the vulnerability by activating SSH on port TCP 5558 to cause disruption to the NMS and NE communication. This issue affects:…
- risk 0.55cvss 8.5epss 0.01
Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X…
- risk 0.54cvss 8.3epss 0.01
The product exposes a service that is intended for local only to all network interfaces without any authentication.
- risk 0.54cvss 8.3epss 0.00
Communication between the client and the server application of the affected products is partially done using CORBA (Common Object Request Broker Architecture) over TCP/IP. This protocol is not encrypted and allows tracing of internal messages. This issue affects * …
- risk 0.53cvss 8.1epss 0.00
A vulnerability exists in REB500 for an authenticated user with low-level privileges to access and alter the content of directories by using the DAC protocol that the user is not authorized to do so.
- risk 0.53cvss 8.1epss 0.00
A vulnerability exists in REB500 for an authenticated user with Installer role to access and alter the contents of directories that the role is not authorized to do so.
- risk 0.53cvss 8.2epss 0.00
An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level is not enabled and only users…
- risk 0.53cvss 8.1epss 0.01
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during…
- risk 0.52cvss 8.0epss 0.00
A user/password reuse vulnerability exists in the FOXMAN-UN/UNEM application and server management. If exploited a malicious high-privileged user could use the passwords and login information through complex routines to extend access on the server and other services.
- risk 0.52cvss 8.0epss 0.00
A vulnerability exists in the web-authentication component of the SDM600. If exploited an attacker could escalate privileges on af-fected installations.
- risk 0.52cvss 8.0epss 0.01
The affected products store both public and private key that are used to sign and protect Custom Parameter Set (CPS) file from modification. An attacker that manages to exploit this vulnerability will be able to change the CPS file, sign it so that it is trusted as the…
- risk 0.51cvss 7.8epss 0.00
This vulnerability allows local attackers to escalate privileges on vulnerable installations of ABB MicroSCADA 9.3 with FP 1-2-3. An attacker must first obtain the ability to execute low-privileged code on the target system in order to exploit this vulnerability. The specific…
- risk 0.50cvss 7.7epss 0.00
A vulnerability exists in the SDM600 API web services authorization validation implementation. An attacker who successfully exploits the vulnerability could read data directly from a data store that is not restricted, or insufficiently protected, having access to sensitive…
- risk 0.50cvss 7.7epss 0.01
Insufficiently Protected Credentials vulnerability in client environment of Hitachi ABB Power Grids Retail Operations and Counterparty Settlement Billing (CSB) allows an attacker or unauthorized user to access database credentials, shut down the product and access or alter. This…
- risk 0.49cvss 7.5epss 0.00
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the…
- risk 0.49cvss 7.6epss 0.00
A vulnerability exists in the too permissive HTTP response header web server settings of the SDM600. An attacker can take advantage of this and possibly carry out privileged actions and access sensitive information.
- risk 0.49cvss 7.5epss 0.01
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the…
- risk 0.49cvss 7.5epss 0.01
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500…
- risk 0.49cvss 7.5epss 0.01
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced…
- risk 0.49cvss 7.5epss 0.00
A vulnerability exists in the SDM600 software. The software operates at a privilege level that is higher than the minimum level required. An attacker who successfully exploits this vulnerability can escalate privileges. This issue affects: All SDM600 versions prior to…
- risk 0.49cvss 7.5epss 0.01
A vulnerability exists in a SDM600 endpoint. An attacker could exploit this vulnerability by running multiple parallel requests, the SDM600 web services become busy rendering the application unresponsive. This issue affects: All SDM600 versions prior to version 1.2 FP3 HF4…
- risk 0.49cvss 7.5epss 0.01
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future…
- risk 0.49cvss 7.5epss 0.01
Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a…
- risk 0.49cvss 7.5epss 0.00
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue…
- risk 0.49cvss 7.5epss 0.01
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500…
- risk 0.49cvss 7.5epss 0.01
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a…
- risk 0.49cvss 7.5epss 0.01
Password autocomplete vulnerability in the web application password field of Hitachi ABB Power Grids eSOMS allows attacker to gain access to user credentials that are stored by the browser. This issue affects: Hitachi ABB Power Grids eSOMS version 6.3 and prior versions.
- risk 0.49cvss 7.5epss 0.02
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of…
- risk 0.49cvss 7.5epss 0.01
Information Exposure vulnerability in Hitachi ABB Power Grids eSOMS allows unauthorized user to gain access to report data if the URL used to access the report is discovered. This issue affects: Hitachi ABB Power Grids eSOMS 6.0 versions prior to 6.0.4.2.2; 6.1 versions prior to…
- risk 0.49cvss 7.6epss 0.01
Lack of input checks for SQL queries in ABB eSOMS versions 3.9 to 6.0.3 might allow an attacker SQL injection attacks against the backend database.
- risk 0.49cvss 7.5epss 0.02
An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service.
- risk 0.49cvss 7.5epss 0.02
ABB Relion 630 devices 1.1 before 1.1.0.C0, 1.2 before 1.2.0.B3, and 1.3 before 1.3.0.A6 allow remote attackers to cause a denial of service (reboot) via a reboot command in an SPA message.
- risk 0.48cvss 7.4epss 0.00
A vulnerability exists in the SOAP Web services of the Asset Suite versions listed below. If successfully exploited, an attacker could gain unauthorized access to the product and the time window of a possible password attack could be expanded.
- risk 0.48cvss 7.4epss 0.00
A vulnerability exists in the FOXMAN-UN/UNEM server that affects the message queueing mechanism’s certificate validation. If exploited an attacker could spoof a trusted entity causing a loss of confidentiality and integrity.
- risk 0.48cvss 7.4epss 0.00
A vulnerability exists in the component RTU500 Scripting interface. When a client connects to a server using TLS, the server presents a certificate. This certificate links a public key to the identity of the service and is signed by a Certification Authority (CA), allowing the…
- risk 0.47cvss 7.3epss 0.00
A vulnerability exists in in the Monitor Pro interface of the MicroSCADA X SYS600 product. An authenticated user with low privileges can see and overwrite files causing information leak and data corruption.
- risk 0.47cvss 7.2epss 0.02
Command injection vulnerability in the Edge Computing UI for the TRO600 series radios that allows for the execution of arbitrary system commands. If exploited, an attacker with write access to the web UI can execute commands on the device with root privileges, far more extensive…
- risk 0.47cvss 7.2epss 0.02
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to…
Page 1 of 3