Unrated severityNVD Advisory· Published Jul 26, 2023· Updated Mar 5, 2025
CVE-2022-2502
CVE-2022-2502
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Affected products
2(expand)+ 1 more
- (no CPE)
- (no CPE)range: RTU500 series CMU Firmware version 13.3.1
Patches
Vulnerability mechanics
References
1- publisher.hitachienergy.com/previewmitrevendor-advisory
News mentions
0No linked articles in our index yet.