Unrated severityNVD Advisory· Published Jul 26, 2023· Updated Mar 5, 2025
CVE-2022-4608
CVE-2022-4608
Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Affected products
2(expand)+ 1 more
- (no CPE)
- (no CPE)range: RTU500 series CMU Firmware version 13.3.1
Patches
Vulnerability mechanics
References
1- publisher.hitachienergy.com/previewmitrevendor-advisory