880 total · sorted by risk| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2018-7242 | Cri | 0.64 | 9.8 | 0.02 | Apr 18, 2018 | Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. | ||
| CVE-2018-7241 | Cri | 0.64 | 9.8 | 0.04 | Apr 18, 2018 | Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. | ||
| CVE-2018-7238 | Cri | 0.64 | 9.8 | 0.03 | Mar 9, 2018 | A buffer overflow vulnerability exist in the web-based GUI of Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to execute arbitrary code. | ||
| CVE-2018-7233 | Cri | 0.64 | 9.8 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'model_name' or 'mac_address'. | ||
| CVE-2018-7232 | Cri | 0.64 | 9.8 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'network.ieee8021x.delete_certs'. | ||
| CVE-2018-7231 | Cri | 0.64 | 9.8 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'system.opkg.remove'. | ||
| CVE-2018-7229 | Cri | 0.64 | 9.8 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and gain administrator privileges because the use of hardcoded credentials. | ||
| CVE-2018-7228 | Cri | 0.64 | 9.8 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and get the administrator privileges. | ||
| CVE-2017-14024 | Cri | 0.64 | 9.8 | 0.06 | Nov 13, 2017 | A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow… | ||
| CVE-2017-13997 | Cri | 0.64 | 9.8 | 0.05 | Oct 3, 2017 | A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server… | ||
| CVE-2017-9957 | Cri | 0.64 | 9.8 | 0.02 | Sep 26, 2017 | A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials. | ||
| CVE-2017-7974 | Cri | 0.64 | 9.8 | 0.05 | Sep 26, 2017 | A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files. | ||
| CVE-2017-7973 | Cri | 0.64 | 9.8 | 0.01 | Sep 26, 2017 | A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database. | ||
| CVE-2017-9629 | Cri | 0.64 | 9.8 | 0.10 | Jul 7, 2017 | A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context… | ||
| CVE-2017-6034 | Cri | 0.64 | 9.8 | 0.05 | Jun 30, 2017 | An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and… | ||
| CVE-2017-6028 | Cri | 0.64 | 9.8 | 0.02 | Jun 30, 2017 | An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing.… | ||
| CVE-2017-5158 | Cri | 0.64 | 9.8 | 0.02 | Apr 20, 2017 | An Information Exposure issue was discovered in Schneider Electric Wonderware InTouch Access Anywhere, version 11.5.2 and prior. Credentials may be exposed to external systems via specific URL parameters, as arbitrary destination addresses may be specified. | ||
| CVE-2017-7689 | Cri | 0.64 | 9.8 | 0.06 | Apr 11, 2017 | A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0. | ||
| CVE-2017-7575 | Cri | 0.64 | 9.8 | 0.04 | Apr 6, 2017 | Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded,… | ||
| CVE-2017-7574 | Cri | 0.64 | 9.8 | 0.01 | Apr 6, 2017 | Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a… | ||
| CVE-2016-5818 | Cri | 0.64 | 9.8 | 0.02 | Feb 13, 2017 | An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device. | ||
| CVE-2016-5815 | Cri | 0.64 | 9.8 | 0.02 | Feb 13, 2017 | An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal… | ||
| CVE-2016-4520 | Cri | 0.64 | 9.8 | 0.06 | Jul 15, 2016 | Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors. | ||
| CVE-2012-0931 | Cri | 0.64 | 9.8 | 0.05 | Jan 28, 2012 | Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors. | ||
| CVE-2022-34753 | Hig | 0.63 | 8.8 | 0.71 | Jul 13, 2022 | A CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote root exploit when the command is compromised. Affected Products: SpaceLogic C-Bus Home Controller (5200WHC2), formerly known as C-Bus… | ||
| CVE-2018-7777 | Hig | 0.63 | 8.8 | 0.32 | Jul 3, 2018 | The vulnerability is due to insufficient handling of update_file request parameter on update_module.php in Schneider Electric U.motion Builder software versions prior to v1.3.4. A remote, authenticated attacker can exploit this vulnerability by sending a crafted request to the… | ||
| CVE-2022-30234 | Cri | 0.61 | 9.4 | 0.01 | Jun 2, 2022 | A CWE-798: Use of Hard-coded Credentials vulnerability exists that could allow arbitrary code to be executed when root level access is obtained. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | ||
| CVE-2021-22823 | Cri | 0.61 | 9.1 | 0.21 | Feb 11, 2022 | A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector… | ||
| CVE-2026-9037 | Cri | 0.60 | — | 0.00 | May 28, 2026 | A firmware update mechanism in the affected charging controller fails to validate the authenticity of firmware packages delivered through the device's management interface. Because cryptographic signatures are not verified, an attacker with the ability to interfere with or… | ||
| CVE-2020-25176 | Cri | 0.60 | 9.1 | 0.06 | Mar 18, 2022 | Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote,… | ||
| CVE-2022-0715 | Cri | 0.60 | 9.1 | 0.06 | Mar 9, 2022 | A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior… | ||
| CVE-2021-22719 | Hig | 0.60 | 8.8 | 0.41 | Apr 13, 2021 | A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in C-Bus Toolkit (V1.15.7 and prior) that could allow a remote code execution when a file is uploaded. | ||
| CVE-2021-22717 | Hig | 0.60 | 8.8 | 0.39 | Apr 13, 2021 | A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in C-Bus Toolkit (V1.15.7 and prior) that could allow a remote code execution when processing config files. | ||
| CVE-2016-5809 | Hig | 0.60 | 8.8 | 0.02 | Feb 13, 2017 | An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of… | ||
| CVE-2025-48017 | Cri | 0.59 | 9.0 | 0.00 | May 20, 2025 | Improper limitation of pathname in Circuit Provisioning and File Import applications allows modification and uploading of files | ||
| CVE-2023-22610 | Cri | 0.59 | 9.1 | 0.01 | Jan 31, 2023 | A CWE-863: Incorrect Authorization vulnerability exists that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port. | ||
| CVE-2021-22795 | Cri | 0.59 | 9.1 | 0.03 | Apr 13, 2022 | A CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote code execution when performed over the network. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior) | ||
| CVE-2021-22794 | Cri | 0.59 | 9.1 | 0.02 | Apr 13, 2022 | A CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior) | ||
| CVE-2021-22805 | Cri | 0.59 | 9.1 | 0.01 | Feb 11, 2022 | A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector… | ||
| CVE-2021-22704 | Cri | 0.59 | 9.1 | 0.01 | Sep 2, 2021 | A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists in Harmony/HMI Products Configured by Vijeo Designer (all versions prior to V6.2 SP11 ), Vijeo Designer Basic (all versions prior to V1.2), or EcoStruxure Machine Expert (all versions… | ||
| CVE-2021-22779 | Cri | 0.59 | 9.1 | 0.01 | Jul 14, 2021 | Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure… | ||
| CVE-2019-6848 | Hig | 0.59 | 8.6 | 0.33 | Oct 29, 2019 | A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 CPU (BMEx58*) and Modicon M580 communication module (BMENOC0311, BMENOC0321) (see notification for version info), which could cause a Denial of Service attack on the PLC when sending… | ||
| CVE-2019-6837 | Cri | 0.59 | 9.1 | 0.01 | Sep 17, 2019 | A Server-Side Request Forgery (SSRF): CWE-918 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could… | ||
| CVE-2019-6816 | Cri | 0.59 | 9.1 | 0.01 | May 22, 2019 | In Modicon Quantum all firmware versions, a CWE-94: Code Injection vulnerability could cause an unauthorized firmware modification with possible Denial of Service when using Modbus protocol. | ||
| CVE-2019-6815 | Cri | 0.59 | 9.1 | 0.01 | May 22, 2019 | In Modicon Quantum all firmware versions, CWE-264: Permissions, Privileges, and Access Control vulnerabilities could cause a denial of service or unauthorized modifications of the PLC configuration when using Ethernet/IP protocol. | ||
| CVE-2018-7245 | Cri | 0.59 | 9.1 | 0.01 | Apr 18, 2018 | An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to change UPS control and… | ||
| CVE-2018-7237 | Cri | 0.59 | 9.1 | 0.02 | Mar 9, 2018 | A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow a remote attacker to delete arbitrary system file due to lack of validation of the /login/bin/set_param to the file name with the value of… | ||
| CVE-2015-7921 | Cri | 0.59 | 9.1 | 0.02 | Apr 6, 2016 | The FTP server in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 has hardcoded credentials, which makes it easier for remote attackers to bypass authentication by leveraging knowledge of these… | ||
| CVE-2018-7801 | Hig | 0.58 | 8.8 | 0.06 | Dec 24, 2018 | A Code Injection vulnerability exists in EVLink Parking, v3.2.0-12_v1 and earlier, which could enable access with maximum privileges when a remote code execution is performed. | ||
| CVE-2026-4827 | Hig | 0.57 | — | 0.00 | May 12, 2026 | CWE‑331: Insufficient Entropy vulnerability exists that could lead to unauthorized access when an attacker on the network can exploit weaknesses in session‑management protections. |
- risk 0.64cvss 9.8epss 0.02
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
- risk 0.64cvss 9.8epss 0.04
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.
- risk 0.64cvss 9.8epss 0.03
A buffer overflow vulnerability exist in the web-based GUI of Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to execute arbitrary code.
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'model_name' or 'mac_address'.
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'network.ieee8021x.delete_certs'.
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow execution of commands due to lack of validation of the shell meta characters with the value of 'system.opkg.remove'.
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and gain administrator privileges because the use of hardcoded credentials.
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow an unauthenticated, remote attacker to bypass authentication and get the administrator privileges.
- risk 0.64cvss 9.8epss 0.06
A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow…
- risk 0.64cvss 9.8epss 0.05
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server…
- risk 0.64cvss 9.8epss 0.02
A vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which the web service contains a hidden system account with a hardcoded password. An attacker can use this information to log into the system with high-privilege credentials.
- risk 0.64cvss 9.8epss 0.05
A path traversal information disclosure vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can execute arbitrary code and exfiltrate files.
- risk 0.64cvss 9.8epss 0.01
A SQL injection vulnerability exists in Schneider Electric's U.motion Builder software versions 1.2.1 and prior in which an unauthenticated user can use calls to various paths allowing performance of arbitrary SQL commands against the underlying database.
- risk 0.64cvss 9.8epss 0.10
A Stack-Based Buffer Overflow issue was discovered in Schneider Electric Wonderware ArchestrA Logger, versions 2017.426.2307.1 and prior. The stack-based buffer overflow vulnerability has been identified, which may allow a remote attacker to execute arbitrary code in the context…
- risk 0.64cvss 9.8epss 0.05
An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and…
- risk 0.64cvss 9.8epss 0.02
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing.…
- risk 0.64cvss 9.8epss 0.02
An Information Exposure issue was discovered in Schneider Electric Wonderware InTouch Access Anywhere, version 11.5.2 and prior. Credentials may be exposed to external systems via specific URL parameters, as arbitrary destination addresses may be specified.
- risk 0.64cvss 9.8epss 0.06
A Command Injection vulnerability in Schneider Electric homeLYnk Controller exists in all versions before 1.5.0.
- risk 0.64cvss 9.8epss 0.04
Schneider Electric Modicon TM221CE16R 1.3.3.3 devices allow remote attackers to discover the application-protection password via a \x00\x01\x00\x00\x00\x05\x01\x5a\x00\x03\x00 request to the Modbus port (502/tcp). Subsequently the application may be arbitrarily downloaded,…
- risk 0.64cvss 9.8epss 0.01
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a…
- risk 0.64cvss 9.8epss 0.02
An issue was discovered in Schneider Electric PowerLogic PM8ECC device 2.651 and older. Undocumented hard-coded credentials allow access to the device.
- risk 0.64cvss 9.8epss 0.02
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal…
- risk 0.64cvss 9.8epss 0.06
Schneider Electric Pelco Digital Sentry Video Management System with firmware before 7.14 has hardcoded credentials, which allows remote attackers to obtain access, and consequently execute arbitrary code, via unspecified vectors.
- risk 0.64cvss 9.8epss 0.05
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
- risk 0.63cvss 8.8epss 0.71
A CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote root exploit when the command is compromised. Affected Products: SpaceLogic C-Bus Home Controller (5200WHC2), formerly known as C-Bus…
- risk 0.63cvss 8.8epss 0.32
The vulnerability is due to insufficient handling of update_file request parameter on update_module.php in Schneider Electric U.motion Builder software versions prior to v1.3.4. A remote, authenticated attacker can exploit this vulnerability by sending a crafted request to the…
- risk 0.61cvss 9.4epss 0.01
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could allow arbitrary code to be executed when root level access is obtained. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior)
- risk 0.61cvss 9.1epss 0.21
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector…
- risk 0.60cvss —epss 0.00
A firmware update mechanism in the affected charging controller fails to validate the authenticity of firmware packages delivered through the device's management interface. Because cryptographic signatures are not verified, an attacker with the ability to interfere with or…
- risk 0.60cvss 9.1epss 0.06
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote,…
- risk 0.60cvss 9.1epss 0.06
A CWE-287: Improper Authentication vulnerability exists that could cause an attacker to arbitrarily change the behavior of the UPS when a key is leaked and used to upload malicious firmware. Affected Product: APC Smart-UPS Family: SMT Series (SMT Series ID=18: UPS 09.8 and prior…
- risk 0.60cvss 8.8epss 0.41
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in C-Bus Toolkit (V1.15.7 and prior) that could allow a remote code execution when a file is uploaded.
- risk 0.60cvss 8.8epss 0.39
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists in C-Bus Toolkit (V1.15.7 and prior) that could allow a remote code execution when processing config files.
- risk 0.60cvss 8.8epss 0.02
An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of…
- risk 0.59cvss 9.0epss 0.00
Improper limitation of pathname in Circuit Provisioning and File Import applications allows modification and uploading of files
- risk 0.59cvss 9.1epss 0.01
A CWE-863: Incorrect Authorization vulnerability exists that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port.
- risk 0.59cvss 9.1epss 0.03
A CWE-78 Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote code execution when performed over the network. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior)
- risk 0.59cvss 9.1epss 0.02
A CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause remote code execution. Affected Product: StruxureWare Data Center Expert (V7.8.1 and prior)
- risk 0.59cvss 9.1epss 0.01
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector…
- risk 0.59cvss 9.1epss 0.01
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists in Harmony/HMI Products Configured by Vijeo Designer (all versions prior to V6.2 SP11 ), Vijeo Designer Basic (all versions prior to V1.2), or EcoStruxure Machine Expert (all versions…
- risk 0.59cvss 9.1epss 0.01
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure…
- risk 0.59cvss 8.6epss 0.33
A CWE-755: Improper Handling of Exceptional Conditions vulnerability exists in Modicon M580 CPU (BMEx58*) and Modicon M580 communication module (BMENOC0311, BMENOC0321) (see notification for version info), which could cause a Denial of Service attack on the PLC when sending…
- risk 0.59cvss 9.1epss 0.01
A Server-Side Request Forgery (SSRF): CWE-918 vulnerability exists in U.motion Server (MEG6501-0001 - U.motion KNX server, MEG6501-0002 - U.motion KNX Server Plus, MEG6260-0410 - U.motion KNX Server Plus, Touch 10, MEG6260-0415 - U.motion KNX Server Plus, Touch 15), which could…
- risk 0.59cvss 9.1epss 0.01
In Modicon Quantum all firmware versions, a CWE-94: Code Injection vulnerability could cause an unauthorized firmware modification with possible Denial of Service when using Modbus protocol.
- risk 0.59cvss 9.1epss 0.01
In Modicon Quantum all firmware versions, CWE-264: Permissions, Privileges, and Access Control vulnerabilities could cause a denial of service or unauthorized modifications of the PLC configuration when using Ethernet/IP protocol.
- risk 0.59cvss 9.1epss 0.01
An improper authorization vulnerability exists In Schneider Electric's 66074 MGE Network Management Card Transverse installed in MGE UPS and MGE STS. The integrated web server (Port 80/443/TCP) of the affected devices could allow a remote attacker to change UPS control and…
- risk 0.59cvss 9.1epss 0.02
A vulnerability exists in Schneider Electric's Pelco Sarix Professional in all firmware versions prior to 3.29.67 which could allow a remote attacker to delete arbitrary system file due to lack of validation of the /login/bin/set_param to the file name with the value of…
- risk 0.59cvss 9.1epss 0.02
The FTP server in Pro-face GP-Pro EX EX-ED before 4.05.000, PFXEXEDV before 4.05.000, PFXEXEDLS before 4.05.000, and PFXEXGRPLS before 4.05.000 has hardcoded credentials, which makes it easier for remote attackers to bypass authentication by leveraging knowledge of these…
- risk 0.58cvss 8.8epss 0.06
A Code Injection vulnerability exists in EVLink Parking, v3.2.0-12_v1 and earlier, which could enable access with maximum privileges when a remote code execution is performed.
- risk 0.57cvss —epss 0.00
CWE‑331: Insufficient Entropy vulnerability exists that could lead to unauthorized access when an attacker on the network can exploit weaknesses in session‑management protections.