VYPR

Modicon M241

by Schneider Electric

CVEs (11)

  • CVE-2017-6026CriJun 30, 2017
    risk 0.65cvss 9.1epss 0.32

    A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are…

  • CVE-2020-7487CriApr 22, 2020
    risk 0.64cvss 9.8epss 0.01

    A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists which could allow the attacker to execute malicious code on the Modicon M218, M241, M251, and M258 controllers.

  • CVE-2017-6034CriJun 30, 2017
    risk 0.64cvss 9.8epss 0.05

    An authentication bypass by capture-replay issue was discovered in Schneider Electric Modicon Modbus Protocol. Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and…

  • CVE-2017-6028CriJun 30, 2017
    risk 0.64cvss 9.8epss 0.02

    An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing.…

  • CVE-2019-6820HigMay 22, 2019
    risk 0.53cvss 8.2epss 0.01

    A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200,…

  • CVE-2021-22699HigMay 26, 2021
    risk 0.49cvss 7.5epss 0.01

    Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior to V5.1.9.1 that could cause denial of service when specific crafted requests are sent to the controller over HTTP.

  • CVE-2020-7488HigApr 22, 2020
    risk 0.49cvss 7.5epss 0.01

    A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers.

  • CVE-2017-6030MedJun 30, 2017
    risk 0.42cvss 6.5epss 0.02

    A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version…

  • CVE-2025-13902MedMar 10, 2026
    risk 0.35cvss 5.4epss 0.00

    CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause condition where authenticated attackers can have a victim’s browser run arbitrary JavaScript when the victim hovers over a maliciously crafted…

  • CVE-2024-6528MedJul 11, 2024
    risk 0.35cvss 5.4epss 0.00

    CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause a vulnerability leading to a cross-site scripting condition where attackers can have a victim’s browser run arbitrary JavaScript when they visit a…

  • CVE-2025-13901MedMar 10, 2026
    risk 0.34cvss 5.3epss 0.00

    CWE-404 Improper Resource Shutdown or Release vulnerability exists that could cause partial Denial of Service on Machine Expert protocol when an unauthenticated attacker sends malicious payload to occupy active communication channels.