Vendor CVEs
Ge
All CVEs
134 total · sorted by risk| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2023-0755 | Cri | 0.65 | 9.8 | 0.12 | Feb 23, 2023 | The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code. | ||
| CVE-2020-27265 | Cri | 0.65 | 9.8 | 0.10 | Jan 14, 2021 | KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server:… | ||
| CVE-2016-5788 | Cri | 0.65 | 10.0 | 0.02 | Nov 25, 2016 | General Electric (GE) Bently Nevada 3500/22M USB with firmware before 5.0 and Bently Nevada 3500/22M Serial have open ports, which makes it easier for remote attackers to obtain privileged access via unspecified vectors. | ||
| CVE-2022-2825 | Cri | 0.64 | 9.8 | 0.03 | Mar 29, 2023 | This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue… | ||
| CVE-2023-0754 | Cri | 0.64 | 9.8 | 0.03 | Feb 23, 2023 | The affected products are vulnerable to an integer overflow or wraparound, which could allow an attacker to crash the server and remotely execute arbitrary code. | ||
| CVE-2022-46732 | Cri | 0.64 | 9.8 | 0.01 | Jan 18, 2023 | Even if the authentication fails for local service authentication, the requested command could still execute regardless of authentication status. | ||
| CVE-2022-43977 | Cri | 0.64 | 9.8 | 0.01 | Jan 17, 2023 | An issue was discovered on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. The debug port accessible via TCP (a qconn service) lacks access control. | ||
| CVE-2022-43976 | Cri | 0.64 | 9.8 | 0.01 | Jan 17, 2023 | An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. Direct access to the API is possible on TCP port 8888 via programs located in the cgi-bin folder without any authentication. | ||
| CVE-2022-24119 | Cri | 0.64 | 9.8 | 0.01 | Dec 26, 2022 | Certain General Electric Renewable Energy products have a hidden feature for unauthenticated remote access to the device configuration shell. This affects iNET and iNET II before 8.3.0. | ||
| CVE-2022-24117 | Cri | 0.64 | 9.8 | 0.00 | Dec 26, 2022 | Certain General Electric Renewable Energy products download firmware without an integrity check. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6. | ||
| CVE-2022-24116 | Cri | 0.64 | 9.8 | 0.00 | Dec 26, 2022 | Certain General Electric Renewable Energy products have inadequate encryption strength. This affects iNET and iNET II before 8.3.0. | ||
| CVE-2021-27428 | Cri | 0.64 | 9.8 | 0.01 | Mar 23, 2022 | GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade… | ||
| CVE-2021-27426 | Cri | 0.64 | 9.8 | 0.01 | Mar 23, 2022 | GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user. | ||
| CVE-2020-25197 | Cri | 0.64 | 9.8 | 0.03 | Mar 18, 2022 | A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system. | ||
| CVE-2021-27440 | Cri | 0.64 | 9.8 | 0.01 | Mar 25, 2021 | The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1). | ||
| CVE-2020-12017 | Cri | 0.64 | 9.8 | 0.02 | Jun 2, 2020 | GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated… | ||
| CVE-2019-6548 | Cri | 0.64 | 9.8 | 0.01 | May 9, 2019 | GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user. | ||
| CVE-2018-10611 | Cri | 0.64 | 9.8 | 0.05 | Jun 4, 2018 | Java remote method invocation (RMI) input port in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior may be exploited to allow unauthenticated users to launch applications and support remote code execution through web services. | ||
| CVE-2017-14008 | Cri | 0.64 | 9.8 | 0.03 | Mar 20, 2018 | GE Centricity PACS RA1000, diagnostic image analysis, all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices. | ||
| CVE-2017-14006 | Cri | 0.64 | 9.8 | 0.02 | Mar 20, 2018 | GE Xeleris versions 1.0,1.1,2.1,3.0,3.1, medical imaging systems, all current versions are affected, these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the… | ||
| CVE-2017-14004 | Cri | 0.64 | 9.8 | 0.02 | Mar 20, 2018 | GE GEMNet License server (EchoServer) all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices. | ||
| CVE-2017-14002 | Cri | 0.64 | 9.8 | 0.05 | Mar 20, 2018 | GE Infinia/Infinia with Hawkeye 4 medical imaging systems all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected… | ||
| CVE-2018-5475 | Cri | 0.64 | 9.8 | 0.04 | Feb 19, 2018 | A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution. | ||
| CVE-2018-5473 | Cri | 0.64 | 9.8 | 0.06 | Feb 19, 2018 | An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote… | ||
| CVE-2017-7905 | Cri | 0.64 | 9.8 | 0.01 | Jun 30, 2017 | A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware… | ||
| CVE-2016-2310 | Cri | 0.64 | 9.8 | 0.03 | Jun 9, 2016 | General Electric (GE) Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware before 5.5.0 and ML810, ML3000, and ML3100 switches with firmware before 5.5.0k have hardcoded credentials, which allows remote attackers to modify configuration settings via the web… | ||
| CVE-2008-0174 | Cri | 0.64 | 9.8 | 0.02 | Jan 29, 2008 | GE Fanuc Proficy Real-Time Information Portal 2.6 and earlier uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the passwords and gain privileges. | ||
| CVE-2016-0861 | Hig | 0.61 | 8.8 | 0.14 | Feb 5, 2016 | General Electric (GE) Industrial Solutions UPS SNMP/Web Adapter devices with firmware before 4.8 allow remote authenticated users to execute arbitrary commands via unspecified vectors. | ||
| CVE-2020-27267 | Cri | 0.60 | 9.1 | 0.05 | Jan 14, 2021 | KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server… | ||
| CVE-2020-27263 | Cri | 0.60 | 9.1 | 0.05 | Jan 14, 2021 | KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server:… | ||
| CVE-2023-5908 | Cri | 0.59 | 9.1 | 0.01 | Nov 30, 2023 | KEPServerEX is vulnerable to a buffer overflow which may allow an attacker to crash the product being accessed or leak information. | ||
| CVE-2022-2848 | Cri | 0.59 | 9.1 | 0.03 | Mar 29, 2023 | This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue… | ||
| CVE-2022-24118 | Cri | 0.59 | 9.1 | 0.01 | Dec 26, 2022 | Certain General Electric Renewable Energy products allow attackers to use a code to trigger a reboot into the factory default configuration. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6. | ||
| CVE-2018-15362 | Cri | 0.59 | 9.1 | 0.03 | Dec 7, 2018 | XXE in GE Proficy Cimplicity GDS versions 9.0 R2, 9.5, 10.0 | ||
| CVE-2020-36549 | Hig | 0.57 | 8.8 | 0.00 | Jun 17, 2022 | A vulnerability classified as critical was found in GE Voluson S8. Affected is the underlying Windows XP operating system. Missing patches might introduce an excessive attack surface. Access to the local network is required for this attack to succeed. | ||
| CVE-2021-27438 | Hig | 0.57 | 8.8 | 0.01 | Mar 25, 2021 | The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1). | ||
| CVE-2019-13554 | Hig | 0.57 | 8.8 | 0.01 | Apr 7, 2020 | GE Mark VIe Controller has an unsecured Telnet protocol that may allow a user to create an authenticated session using generic default credentials. GE recommends that users disable the Telnet service. | ||
| CVE-2021-27430 | Hig | 0.55 | 8.4 | 0.00 | Mar 23, 2022 | GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR. | ||
| CVE-2012-6663 | Hig | 0.53 | 7.5 | 0.09 | Jan 23, 2020 | General Electric D20ME devices are not properly configured and reveal plaintext passwords. | ||
| CVE-2018-10615 | Hig | 0.53 | 8.1 | 0.03 | Jun 4, 2018 | Directory traversal may lead to files being exfiltrated or deleted on the GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior host platform. | ||
| CVE-2023-4487 | Hig | 0.51 | 7.8 | 0.00 | Sep 5, 2023 | GE CIMPLICITY 2023 is by a process control vulnerability, which could allow a local attacker to insert malicious configuration files in the expected web server execution path to escalate privileges and gain full control of the HMI software. | ||
| CVE-2023-0598 | Hig | 0.51 | 7.8 | 0.01 | Mar 16, 2023 | GE Digital Proficy iFIX 2022, GE Digital Proficy iFIX v6.1, and GE Digital Proficy iFIX v6.5 are vulnerable to code injection, which may allow an attacker to insert malicious configuration files in the expected web server execution path and gain full control of the HMI… | ||
| CVE-2022-3092 | Hig | 0.51 | 7.8 | 0.00 | Dec 8, 2022 | GE CIMPICITY versions 2022 and prior is vulnerable to an out-of-bounds write, which could allow an attacker to execute arbitrary code. | ||
| CVE-2022-3084 | Hig | 0.51 | 7.8 | 0.00 | Dec 8, 2022 | GE CIMPICITY versions 2022 and prior is vulnerable when data from a faulting address controls code flow starting at gmmiObj!CGmmiRootOptionTable, which could allow an attacker to execute arbitrary code. | ||
| CVE-2022-2952 | Hig | 0.51 | 7.8 | 0.00 | Dec 7, 2022 | GE CIMPICITY versions 2022 and prior is vulnerable when data from a faulting address controls code flow starting at gmmiObj!CGmmiOptionContainer, which could allow an attacker to execute arbitrary code. | ||
| CVE-2022-2948 | Hig | 0.51 | 7.8 | 0.00 | Dec 7, 2022 | GE CIMPICITY versions 2022 and prior is vulnerable to a heap-based buffer overflow, which could allow an attacker to execute arbitrary code. | ||
| CVE-2022-2002 | Hig | 0.51 | 7.8 | 0.00 | Dec 7, 2022 | GE CIMPICITY versions 2022 and prior is vulnerable when data from faulting address controls code flow starting at gmmiObj!CGmmiOptionContainer, which could allow an attacker to execute arbitrary code. | ||
| CVE-2021-27454 | Hig | 0.51 | 7.8 | 0.00 | Mar 25, 2021 | The software performs an operation at a privilege level higher than the minimum level required, which creates new weaknesses or amplifies the consequences of other weaknesses on the Reason DR60 (all firmware versions prior to 02A04.1). | ||
| CVE-2021-27452 | Hig | 0.51 | 7.8 | 0.00 | Mar 25, 2021 | The software contains a hard-coded password that could allow an attacker to take control of the merging unit using these hard-coded credentials on the MU320E (all firmware versions prior to v04A00.1). | ||
| CVE-2021-27450 | Hig | 0.51 | 7.8 | 0.00 | Mar 25, 2021 | SSH server configuration file does not implement some best practices. This could lead to a weakening of the SSH protocol strength, which could lead to additional misconfiguration or be leveraged as part of a larger attack on the MU320E (all firmware versions prior to v04A00.1). |
- risk 0.65cvss 9.8epss 0.12
The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code.
- risk 0.65cvss 9.8epss 0.10
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server:…
- risk 0.65cvss 10.0epss 0.02
General Electric (GE) Bently Nevada 3500/22M USB with firmware before 5.0 and Bently Nevada 3500/22M Serial have open ports, which makes it easier for remote attackers to obtain privileged access via unspecified vectors.
- risk 0.64cvss 9.8epss 0.03
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue…
- risk 0.64cvss 9.8epss 0.03
The affected products are vulnerable to an integer overflow or wraparound, which could allow an attacker to crash the server and remotely execute arbitrary code.
- risk 0.64cvss 9.8epss 0.01
Even if the authentication fails for local service authentication, the requested command could still execute regardless of authentication status.
- risk 0.64cvss 9.8epss 0.01
An issue was discovered on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. The debug port accessible via TCP (a qconn service) lacks access control.
- risk 0.64cvss 9.8epss 0.01
An issue was discovered in FC46-WebBridge on GE Grid Solutions MS3000 devices before 3.7.6.25p0_3.2.2.17p0_4.7p0. Direct access to the API is possible on TCP port 8888 via programs located in the cgi-bin folder without any authentication.
- risk 0.64cvss 9.8epss 0.01
Certain General Electric Renewable Energy products have a hidden feature for unauthenticated remote access to the device configuration shell. This affects iNET and iNET II before 8.3.0.
- risk 0.64cvss 9.8epss 0.00
Certain General Electric Renewable Energy products download firmware without an integrity check. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6.
- risk 0.64cvss 9.8epss 0.00
Certain General Electric Renewable Energy products have inadequate encryption strength. This affects iNET and iNET II before 8.3.0.
- risk 0.64cvss 9.8epss 0.01
GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade…
- risk 0.64cvss 9.8epss 0.01
GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user.
- risk 0.64cvss 9.8epss 0.03
A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system.
- risk 0.64cvss 9.8epss 0.01
The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1).
- risk 0.64cvss 9.8epss 0.02
GE Grid Solutions Reason RT Clocks, RT430, RT431, and RT434, all firmware versions prior to 08A05. The device’s vulnerability in the web application could allow multiple unauthenticated attacks that could cause serious impact. The vulnerability may allow an unauthenticated…
- risk 0.64cvss 9.8epss 0.01
GE Communicator, all versions prior to 4.0.517, contains two backdoor accounts with hardcoded credentials, which may allow control over the database. This service is inaccessible to attackers if Windows default firewall settings are used by the end user.
- risk 0.64cvss 9.8epss 0.05
Java remote method invocation (RMI) input port in GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior may be exploited to allow unauthenticated users to launch applications and support remote code execution through web services.
- risk 0.64cvss 9.8epss 0.03
GE Centricity PACS RA1000, diagnostic image analysis, all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
- risk 0.64cvss 9.8epss 0.02
GE Xeleris versions 1.0,1.1,2.1,3.0,3.1, medical imaging systems, all current versions are affected, these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the…
- risk 0.64cvss 9.8epss 0.02
GE GEMNet License server (EchoServer) all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected devices.
- risk 0.64cvss 9.8epss 0.05
GE Infinia/Infinia with Hawkeye 4 medical imaging systems all current versions are affected these devices use default or hard-coded credentials. Successful exploitation of this vulnerability may allow a remote attacker to bypass authentication and gain access to the affected…
- risk 0.64cvss 9.8epss 0.04
A Stack-based Buffer Overflow issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. Multiple stack-based buffer overflow vulnerabilities have been identified, which may allow remote code execution.
- risk 0.64cvss 9.8epss 0.06
An Improper Restriction of Operations within the Bounds of a Memory Buffer issue was discovered in GE D60 Line Distance Relay devices running firmware Version 7.11 and prior. The SSH functions of the device are vulnerable to buffer overflow conditions that may allow a remote…
- risk 0.64cvss 9.8epss 0.01
A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware…
- risk 0.64cvss 9.8epss 0.03
General Electric (GE) Multilink ML800, ML1200, ML1600, and ML2400 switches with firmware before 5.5.0 and ML810, ML3000, and ML3100 switches with firmware before 5.5.0k have hardcoded credentials, which allows remote attackers to modify configuration settings via the web…
- risk 0.64cvss 9.8epss 0.02
GE Fanuc Proficy Real-Time Information Portal 2.6 and earlier uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the passwords and gain privileges.
- risk 0.61cvss 8.8epss 0.14
General Electric (GE) Industrial Solutions UPS SNMP/Web Adapter devices with firmware before 4.8 allow remote authenticated users to execute arbitrary commands via unspecified vectors.
- risk 0.60cvss 9.1epss 0.05
KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server…
- risk 0.60cvss 9.1epss 0.05
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server:…
- risk 0.59cvss 9.1epss 0.01
KEPServerEX is vulnerable to a buffer overflow which may allow an attacker to crash the product being accessed or leak information.
- risk 0.59cvss 9.1epss 0.03
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue…
- risk 0.59cvss 9.1epss 0.01
Certain General Electric Renewable Energy products allow attackers to use a code to trigger a reboot into the factory default configuration. This affects iNET and iNET II before 8.3.0, SD before 6.4.7, TD220X before 2.0.16, and TD220MAX before 1.2.6.
- risk 0.59cvss 9.1epss 0.03
XXE in GE Proficy Cimplicity GDS versions 9.0 R2, 9.5, 10.0
- risk 0.57cvss 8.8epss 0.00
A vulnerability classified as critical was found in GE Voluson S8. Affected is the underlying Windows XP operating system. Missing patches might introduce an excessive attack surface. Access to the local network is required for this attack to succeed.
- risk 0.57cvss 8.8epss 0.01
The software contains a hard-coded password it uses for its own inbound authentication or for outbound communication to external components on the Reason DR60 (all firmware versions prior to 02A04.1).
- risk 0.57cvss 8.8epss 0.01
GE Mark VIe Controller has an unsecured Telnet protocol that may allow a user to create an authenticated session using generic default credentials. GE recommends that users disable the Telnet service.
- risk 0.55cvss 8.4epss 0.00
GE UR bootloader binary Version 7.00, 7.01 and 7.02 included unused hardcoded credentials. Additionally, a user with physical access to the UR IED can interrupt the boot sequence by rebooting the UR.
- risk 0.53cvss 7.5epss 0.09
General Electric D20ME devices are not properly configured and reveal plaintext passwords.
- risk 0.53cvss 8.1epss 0.03
Directory traversal may lead to files being exfiltrated or deleted on the GE MDS PulseNET and MDS PulseNET Enterprise version 3.2.1 and prior host platform.
- risk 0.51cvss 7.8epss 0.00
GE CIMPLICITY 2023 is by a process control vulnerability, which could allow a local attacker to insert malicious configuration files in the expected web server execution path to escalate privileges and gain full control of the HMI software.
- risk 0.51cvss 7.8epss 0.01
GE Digital Proficy iFIX 2022, GE Digital Proficy iFIX v6.1, and GE Digital Proficy iFIX v6.5 are vulnerable to code injection, which may allow an attacker to insert malicious configuration files in the expected web server execution path and gain full control of the HMI…
- risk 0.51cvss 7.8epss 0.00
GE CIMPICITY versions 2022 and prior is vulnerable to an out-of-bounds write, which could allow an attacker to execute arbitrary code.
- risk 0.51cvss 7.8epss 0.00
GE CIMPICITY versions 2022 and prior is vulnerable when data from a faulting address controls code flow starting at gmmiObj!CGmmiRootOptionTable, which could allow an attacker to execute arbitrary code.
- risk 0.51cvss 7.8epss 0.00
GE CIMPICITY versions 2022 and prior is vulnerable when data from a faulting address controls code flow starting at gmmiObj!CGmmiOptionContainer, which could allow an attacker to execute arbitrary code.
- risk 0.51cvss 7.8epss 0.00
GE CIMPICITY versions 2022 and prior is vulnerable to a heap-based buffer overflow, which could allow an attacker to execute arbitrary code.
- risk 0.51cvss 7.8epss 0.00
GE CIMPICITY versions 2022 and prior is vulnerable when data from faulting address controls code flow starting at gmmiObj!CGmmiOptionContainer, which could allow an attacker to execute arbitrary code.
- risk 0.51cvss 7.8epss 0.00
The software performs an operation at a privilege level higher than the minimum level required, which creates new weaknesses or amplifies the consequences of other weaknesses on the Reason DR60 (all firmware versions prior to 02A04.1).
- risk 0.51cvss 7.8epss 0.00
The software contains a hard-coded password that could allow an attacker to take control of the merging unit using these hard-coded credentials on the MU320E (all firmware versions prior to v04A00.1).
- risk 0.51cvss 7.8epss 0.00
SSH server configuration file does not implement some best practices. This could lead to a weakening of the SSH protocol strength, which could lead to additional misconfiguration or be leveraged as part of a larger attack on the MU320E (all firmware versions prior to v04A00.1).
Page 1 of 3