VYPR

Simatic S7 1500 CPU Firmware

by Siemens Foundation

CVEs (36)

  • CVE-2017-2680MedMay 11, 2017
    risk 0.42cvss 6.5epss 0.01

    Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.

  • CVE-2021-44694MedDec 13, 2022
    risk 0.36cvss 5.5epss 0.01

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2022-25622MedApr 12, 2022
    risk 0.35cvss 5.3epss 0.01

    The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on…

  • CVE-2016-2201MedFeb 8, 2016
    risk 0.35cvss 5.3epss 0.03

    Siemens SIMATIC S7-1500 CPU devices before 1.8.3 allow remote attackers to bypass a replay protection mechanism via packets on TCP port 102.

  • CVE-2021-44695MedDec 13, 2022
    risk 0.32cvss 4.9epss 0.01

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2021-44693MedDec 13, 2022
    risk 0.32cvss 4.9epss 0.01

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2014-5074Aug 17, 2014
    risk 0.04cvss epss 0.10

    Siemens SIMATIC S7-1500 CPU devices with firmware before 1.6 allow remote attackers to cause a denial of service (device restart and STOP transition) via crafted TCP packets.

  • CVE-2014-2259Mar 16, 2014
    risk 0.00cvss epss 0.04

    Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTPS packets.

  • CVE-2014-2257Mar 16, 2014
    risk 0.00cvss epss 0.03

    Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets.

  • CVE-2014-2255Mar 16, 2014
    risk 0.00cvss epss 0.04

    Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted HTTP packets.

  • CVE-2014-2253Mar 16, 2014
    risk 0.00cvss epss 0.01

    Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted Profinet packets.

  • CVE-2014-2251Mar 16, 2014
    risk 0.00cvss epss 0.03

    The random-number generator on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors.

  • CVE-2014-2249Mar 16, 2014
    risk 0.00cvss epss 0.01

    Cross-site request forgery (CSRF) vulnerability on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 and SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors.

  • CVE-2014-2248Mar 16, 2014
    risk 0.00cvss epss 0.02

    Open redirect vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via unspecified vectors.

  • CVE-2014-2247Mar 16, 2014
    risk 0.00cvss epss 0.02

    The integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject headers via unspecified vectors.

  • CVE-2014-2246Mar 16, 2014
    risk 0.00cvss epss 0.02

    Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.

Page 2 of 2