VYPR

SIMATIC CP 1242-7 V2 (incl. SIPLUS variants)

by Siemens Foundation

CVEs (32)

  • CVE-2017-12741HigDec 26, 2017
    risk 0.49cvss 7.5epss 0.05

    Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.

  • CVE-2017-2681MedMay 11, 2017
    risk 0.42cvss 6.5epss 0.00

    Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.

  • CVE-2017-2680MedMay 11, 2017
    risk 0.42cvss 6.5epss 0.02

    Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.

  • CVE-2023-30755MedSep 10, 2024
    risk 0.29cvss 4.4epss 0.00

    A vulnerability has been identified in SIMATIC CP 1242-7 V2 (incl. SIPLUS variants) (All versions < V3.5.20), SIMATIC CP 1243-1 (incl. SIPLUS variants) (All versions < V3.5.20), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.5.20), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.5.20), SIMATIC CP 1243-7 LTE (All versions < V3.5.20), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.5.20), SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions), SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions), SIMATIC WinCC Runtime Advanced (All versions), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.4.8), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.4.8). The web server of the affected devices do not properly handle the shutdown or reboot request, which could lead to the clean up of certain resources. This could allow a remote attacker with elevated privileges to cause a denial of service condition in the system.

  • CVE-2023-38380Dec 12, 2023
    risk 0.00cvss epss 0.00

    A vulnerability has been identified in SIMATIC CP 1242-7 V2 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543-1 (6GK7543-1AX00-0XE0) (All versions < V3.0.37), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SINAMICS S210 (6SL5...) (All versions >= V6.1 < V6.1 HF2), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1543-1 (6AG1543-1AX00-2XE0) (All versions < V3.0.37). The webserver implementation of the affected products does not correctly release allocated memory after it has been used. An attacker with network access could use this vulnerability to cause a denial-of-service condition in the webserver of the affected product.

  • CVE-2022-43768Apr 11, 2023
    risk 0.00cvss epss 0.01

    A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.

  • CVE-2022-43767Apr 11, 2023
    risk 0.00cvss epss 0.01

    A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.

  • CVE-2022-43716Apr 11, 2023
    risk 0.00cvss epss 0.01

    A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation which leads to a restart of the webserver of the affected product.

  • CVE-2021-44695Dec 13, 2022
    risk 0.00cvss epss 0.00

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2021-44693Dec 13, 2022
    risk 0.00cvss epss 0.00

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2021-44694Dec 13, 2022
    risk 0.00cvss epss 0.00

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2021-40365Dec 13, 2022
    risk 0.00cvss epss 0.00

    Affected devices don't process correctly certain special crafted packets sent to port 102/tcp, which could allow an attacker to cause a denial of service in the device.

  • CVE-2022-30694Nov 8, 2022
    risk 0.00cvss epss 0.00

    The login endpoint /FormLogin in affected web services does not apply proper origin checking. This could allow authenticated remote attackers to track the activities of other users via a login cross-site request forgery attack.

  • CVE-2022-38465Oct 11, 2022
    risk 0.00cvss epss 0.00

    A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINUMERIK MC (All versions < V6.21), SINUMERIK ONE (All versions < V6.21). Affected products protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication. This could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.

  • CVE-2021-37205Feb 9, 2022
    risk 0.00cvss epss 0.01

    A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

  • CVE-2021-37204Feb 9, 2022
    risk 0.00cvss epss 0.02

    A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 Ready4Linux (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packet over port 102/tcp. A restart of the affected device is needed to restore normal operations.

  • CVE-2021-37185Feb 9, 2022
    risk 0.00cvss epss 0.02

    A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

  • CVE-2021-33737Sep 14, 2021
    risk 0.00cvss epss 0.00

    A vulnerability has been identified in SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 ERPC (All versions), SIMATIC CP 343-1 Lean (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3). Sending a specially crafted packet to port 102/tcp of an affected device could cause a denial of service condition. A restart is needed to restore normal operations.

  • CVE-2021-33716Sep 14, 2021
    risk 0.00cvss epss 0.00

    A vulnerability has been identified in SIMATIC CP 1543-1 (incl. SIPLUS variants) (All versions < V3.0), SIMATIC CP 1545-1 (All versions < V1.1). An attacker with access to the subnet of the affected device could retrieve sensitive information stored in cleartext.

  • CVE-2021-37172Aug 10, 2021
    risk 0.00cvss epss 0.00

    A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (V4.5.0). Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.