Vendor CVEs
Iconics
All CVEs
28 total · sorted by risk| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2022-33318 | Cri | 0.67 | 9.8 | 0.45 | Jul 20, 2022 | Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics… | ||
| CVE-2020-12011 | Cri | 0.66 | 9.8 | 0.29 | Jul 16, 2020 | A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition or allow remote code execution. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; MC Works32 version 3.00A… | ||
| CVE-2022-23128 | Cri | 0.64 | 9.8 | 0.03 | Jan 21, 2022 | Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97… | ||
| CVE-2020-12007 | Cri | 0.64 | 9.8 | 0.04 | Jul 16, 2020 | A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all… | ||
| CVE-2020-12013 | Cri | 0.59 | 9.1 | 0.03 | Jul 16, 2020 | A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A… | ||
| CVE-2022-33319 | Hig | 0.53 | 8.2 | 0.02 | Jul 20, 2022 | Out-of-bounds Read vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital… | ||
| CVE-2024-7587 | Hig | 0.51 | 7.8 | 0.00 | Oct 22, 2024 | Incorrect Default Permissions vulnerability in GenBroker32, which is included in the installers for Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite… | ||
| CVE-2022-33320 | Hig | 0.51 | 7.8 | 0.00 | Jul 20, 2022 | Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics… | ||
| CVE-2022-33317 | Hig | 0.51 | 7.8 | 0.00 | Jul 20, 2022 | Inclusion of Functionality from Untrusted Control Sphere vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1,… | ||
| CVE-2022-33316 | Hig | 0.51 | 7.8 | 0.00 | Jul 20, 2022 | Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics… | ||
| CVE-2022-33315 | Hig | 0.51 | 7.8 | 0.00 | Jul 20, 2022 | Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics… | ||
| CVE-2021-27041 | Hig | 0.51 | 7.8 | 0.02 | Jun 25, 2021 | A maliciously crafted DWG file can be used to write beyond the allocated buffer while parsing DWG files. This vulnerability can be exploited to execute arbitrary code | ||
| CVE-2022-29834 | Hig | 0.49 | 7.5 | 0.02 | Jul 20, 2022 | Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions… | ||
| CVE-2020-12015 | Hig | 0.49 | 7.5 | 0.02 | Jul 16, 2020 | A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition due to improper deserialization. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC… | ||
| CVE-2020-12009 | Hig | 0.49 | 7.5 | 0.04 | Jul 16, 2020 | A specially crafted communication packet sent to the affected device could cause a denial-of-service condition due to a deserialization vulnerability. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC… | ||
| CVE-2016-2289 | Hig | 0.49 | 7.5 | 0.02 | Apr 1, 2016 | Directory traversal vulnerability in ICONICS WebHMI 9 and earlier allows remote attackers to read configuration files, and consequently discover password hashes, via unspecified vectors. | ||
| CVE-2024-1574 | Med | 0.44 | 6.7 | 0.00 | Jul 4, 2024 | Use of Externally-Controlled Input to Select Classes or Code ('Unsafe Reflection') vulnerability in the licensing feature of Mitsubishi Electric GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Hyper… | ||
| CVE-2022-40264 | Med | 0.41 | 6.3 | 0.00 | Dec 14, 2022 | Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in ICONICS/Mitsubishi Electric GENESIS64 versions 10.96 to 10.97.2 allows an unauthenticated attacker to create, tamper with or destroy arbitrary files by getting a legitimate user… | ||
| CVE-2022-23127 | Med | 0.40 | 6.1 | 0.02 | Jan 21, 2022 | Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any… | ||
| CVE-2022-23130 | Med | 0.38 | 5.9 | 0.01 | Jan 21, 2022 | Buffer Over-read vulnerability in Mitsubishi Electric MC Works64 versions 4.00A to 4.04E, Mitsubishi Electric GENESIS64 versions 10.97 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 and prior, Mitsubishi Electric ICONICS Suite versions 10.97… | ||
| CVE-2022-23129 | Med | 0.36 | 5.5 | 0.00 | Jan 21, 2022 | Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally.… | ||
| CVE-2021-27040 | Low | 0.22 | 3.3 | 0.03 | Jun 25, 2021 | A maliciously crafted DWG file can be forced to read beyond allocated boundaries when parsing the DWG file. This vulnerability can be exploited to execute arbitrary code. | ||
| CVE-2011-2089 | 0.06 | — | 0.38 | May 13, 2011 | Stack-based buffer overflow in the SetActiveXGUID method in the VersionInfo ActiveX control in GenVersion.dll 8.0.138.0 in the WebHMI subsystem in ICONICS BizViz 9.x before 9.22 and GENESIS32 9.x before 9.22 allows remote attackers to execute arbitrary code via a long string in… | |||
| CVE-2006-6488 | 0.04 | — | 0.08 | Dec 31, 2006 | Stack-based buffer overflow in the DoModal function in the Dialog Wrapper Module ActiveX control (DlgWrapper.dll) before 8.4.166.0, as used by ICONICS OPC Enabled Gauge, Switch, and Vessel ActiveX, allows remote attackers to execute arbitrary code via a long (1) FileName or (2)… | |||
| CVE-2014-0758 | 0.00 | — | 0.02 | Feb 24, 2014 | An ActiveX control in GenLaunch.htm in ICONICS GENESIS32 8.0, 8.02, 8.04, and 8.05 allows remote attackers to execute arbitrary programs via a crafted HTML document. | |||
| CVE-2012-3018 | 0.00 | — | 0.00 | Jul 31, 2012 | The lockout-recovery feature in the Security Configurator component in ICONICS GENESIS32 9.22 and earlier and BizViz 9.22 and earlier uses an improper encryption algorithm for generation of an authentication code, which allows local users to bypass intended access restrictions… | |||
| CVE-2011-5089 | 0.00 | — | 0.04 | Apr 18, 2012 | Buffer overflow in the Security Login ActiveX controls in ICONICS GENESIS32 8.05, 9.0, 9.1, and 9.2 and BizViz 8.05, 9.0, 9.1, and 9.2 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a long password. | |||
| CVE-2011-5088 | 0.00 | — | 0.03 | Apr 18, 2012 | The GENESIS32 IcoSetServer ActiveX control in ICONICS GENESIS32 9.21 and BizViz 9.21 configures the trusted zone on the basis of user input, which allows remote attackers to execute arbitrary code via a crafted web site, related to a "Workbench32/WebHMI component SetTrustedZone… |
- risk 0.67cvss 9.8epss 0.45
Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics…
- risk 0.66cvss 9.8epss 0.29
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition or allow remote code execution. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; MC Works32 version 3.00A…
- risk 0.64cvss 9.8epss 0.03
Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97…
- risk 0.64cvss 9.8epss 0.04
A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all…
- risk 0.59cvss 9.1epss 0.03
A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A…
- risk 0.53cvss 8.2epss 0.02
Out-of-bounds Read vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital…
- risk 0.51cvss 7.8epss 0.00
Incorrect Default Permissions vulnerability in GenBroker32, which is included in the installers for Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite…
- risk 0.51cvss 7.8epss 0.00
Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics…
- risk 0.51cvss 7.8epss 0.00
Inclusion of Functionality from Untrusted Control Sphere vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1,…
- risk 0.51cvss 7.8epss 0.00
Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics…
- risk 0.51cvss 7.8epss 0.00
Deserialization of Untrusted Data vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions 10.97 to 10.97.1, Mitsubishi Electric Iconics…
- risk 0.51cvss 7.8epss 0.02
A maliciously crafted DWG file can be used to write beyond the allocated buffer while parsing DWG files. This vulnerability can be exploited to execute arbitrary code
- risk 0.49cvss 7.5epss 0.02
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 to 10.97.1, Mitsubishi Electric ICONICS Suite versions…
- risk 0.49cvss 7.5epss 0.02
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition due to improper deserialization. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC…
- risk 0.49cvss 7.5epss 0.04
A specially crafted communication packet sent to the affected device could cause a denial-of-service condition due to a deserialization vulnerability. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC…
- risk 0.49cvss 7.5epss 0.02
Directory traversal vulnerability in ICONICS WebHMI 9 and earlier allows remote attackers to read configuration files, and consequently discover password hashes, via unspecified vectors.
- risk 0.44cvss 6.7epss 0.00
Use of Externally-Controlled Input to Select Classes or Code ('Unsafe Reflection') vulnerability in the licensing feature of Mitsubishi Electric GENESIS64 versions 10.97.2 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.2 and prior, Mitsubishi Electric Hyper…
- risk 0.41cvss 6.3epss 0.00
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in ICONICS/Mitsubishi Electric GENESIS64 versions 10.96 to 10.97.2 allows an unauthenticated attacker to create, tamper with or destroy arbitrary files by getting a legitimate user…
- risk 0.40cvss 6.1epss 0.02
Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any…
- risk 0.38cvss 5.9epss 0.01
Buffer Over-read vulnerability in Mitsubishi Electric MC Works64 versions 4.00A to 4.04E, Mitsubishi Electric GENESIS64 versions 10.97 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97 and prior, Mitsubishi Electric ICONICS Suite versions 10.97…
- risk 0.36cvss 5.5epss 0.00
Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally.…
- risk 0.22cvss 3.3epss 0.03
A maliciously crafted DWG file can be forced to read beyond allocated boundaries when parsing the DWG file. This vulnerability can be exploited to execute arbitrary code.
- CVE-2011-2089May 13, 2011risk 0.06cvss —epss 0.38
Stack-based buffer overflow in the SetActiveXGUID method in the VersionInfo ActiveX control in GenVersion.dll 8.0.138.0 in the WebHMI subsystem in ICONICS BizViz 9.x before 9.22 and GENESIS32 9.x before 9.22 allows remote attackers to execute arbitrary code via a long string in…
- CVE-2006-6488Dec 31, 2006risk 0.04cvss —epss 0.08
Stack-based buffer overflow in the DoModal function in the Dialog Wrapper Module ActiveX control (DlgWrapper.dll) before 8.4.166.0, as used by ICONICS OPC Enabled Gauge, Switch, and Vessel ActiveX, allows remote attackers to execute arbitrary code via a long (1) FileName or (2)…
- CVE-2014-0758Feb 24, 2014risk 0.00cvss —epss 0.02
An ActiveX control in GenLaunch.htm in ICONICS GENESIS32 8.0, 8.02, 8.04, and 8.05 allows remote attackers to execute arbitrary programs via a crafted HTML document.
- CVE-2012-3018Jul 31, 2012risk 0.00cvss —epss 0.00
The lockout-recovery feature in the Security Configurator component in ICONICS GENESIS32 9.22 and earlier and BizViz 9.22 and earlier uses an improper encryption algorithm for generation of an authentication code, which allows local users to bypass intended access restrictions…
- CVE-2011-5089Apr 18, 2012risk 0.00cvss —epss 0.04
Buffer overflow in the Security Login ActiveX controls in ICONICS GENESIS32 8.05, 9.0, 9.1, and 9.2 and BizViz 8.05, 9.0, 9.1, and 9.2 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a long password.
- CVE-2011-5088Apr 18, 2012risk 0.00cvss —epss 0.03
The GENESIS32 IcoSetServer ActiveX control in ICONICS GENESIS32 9.21 and BizViz 9.21 configures the trusted zone on the basis of user input, which allows remote attackers to execute arbitrary code via a crafted web site, related to a "Workbench32/WebHMI component SetTrustedZone…