Race Condition in Autonomy Logic OpenPLC Runtime Allows Unauthenticated Admin Account Creation
A critical race condition vulnerability in Autonomy Logic OpenPLC Runtime can allow unauthenticated attackers to create multiple administrative accounts, posing a significant risk to industrial control systems.

CISA has issued an advisory detailing a critical vulnerability, identified as CVE-2026-126088, affecting Autonomy Logic's OpenPLC Runtime software. The vulnerability, present in versions 4.2.4 and prior, stems from a race condition that can be exploited by unauthenticated attackers.
The core of the issue lies in improper synchronization when handling concurrent requests. Attackers can send multiple requests simultaneously, exploiting a timing window where the system checks for the existence of a user before committing it. This allows for the creation of multiple administrative accounts without any prior authentication, granting unauthorized access and control over the OpenPLC Runtime.
The potential impact of this vulnerability is severe, particularly given that OpenPLC Runtime is deployed in critical infrastructure sectors worldwide. These sectors include critical manufacturing, energy, transportation systems, and water and wastewater systems. Successful exploitation could lead to significant disruptions, data manipulation, or even complete system compromise, with far-reaching consequences for essential services.
The Common Vulnerability Scoring System (CVSS) v3.1 base score for this vulnerability is 8.1 HIGH, with a CVSS v4.0 score of 9.2 CRITICAL. The vector string indicates network accessibility, a high complexity for exploitation, no privileges required, and no user interaction needed, highlighting the ease with which an attacker could leverage this flaw.
Autonomy Logic has released a fix for this vulnerability. Users are strongly advised to update their OpenPLC Runtime installations to version 4.3.0 or later to remediate CVE-2026-126088. This update is crucial for protecting against potential exploitation.
In addition to applying the vendor fix, CISA recommends implementing broader defensive measures to minimize risk. These include minimizing network exposure of control system devices, isolating them behind firewalls, and using secure methods like VPNs for remote access. Organizations should also conduct thorough impact and risk assessments before deploying any security measures.
While no known public exploitation targeting these specific vulnerabilities has been reported to CISA at this time, the critical nature of the affected systems and the ease of exploitation warrant immediate attention. Proactive security practices and timely patching are essential for maintaining the integrity and availability of industrial control systems.
This vulnerability was reported to CISA by Noureddin Lutfi. CISA encourages organizations to report any suspected malicious activity to aid in tracking and correlation with other incidents.