| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2019-19300 | Hig | 0.49 | 7.5 | 0.01 | Apr 14, 2020 | A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0),… | ||
| CVE-2019-13946 | Hig | 0.49 | 7.5 | 0.01 | Feb 11, 2020 | Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that… | ||
| CVE-2019-10936 | Hig | 0.49 | 7.5 | 0.02 | Oct 10, 2019 | Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition. | ||
| CVE-2017-12741 | Hig | 0.49 | 7.5 | 0.03 | Dec 26, 2017 | Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. | ||
| CVE-2017-2681 | Med | 0.42 | 6.5 | 0.01 | May 11, 2017 | Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. | ||
| CVE-2017-2680 | Med | 0.42 | 6.5 | 0.01 | May 11, 2017 | Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected. |
- risk 0.49cvss 7.5epss 0.01
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0),…
- risk 0.49cvss 7.5epss 0.01
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that…
- risk 0.49cvss 7.5epss 0.02
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.
- risk 0.49cvss 7.5epss 0.03
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
- risk 0.42cvss 6.5epss 0.01
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.
- risk 0.42cvss 6.5epss 0.01
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.