Relion Sam600 Io Firmware
CVEs (6)
| CVE | Vendor / Product | Sev | Risk | CVSS | EPSS | KEV | Published | Description |
|---|---|---|---|---|---|---|---|---|
| CVE-2021-35535 | Hig | 0.53 | 8.1 | 0.01 | Nov 18, 2021 | Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during… | ||
| CVE-2021-27196 | Hig | 0.49 | 7.5 | 0.02 | Jun 14, 2021 | Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of… | ||
| CVE-2021-35534 | Hig | 0.47 | 7.2 | 0.02 | Nov 18, 2021 | Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to… | ||
| CVE-2023-4518 | Med | 0.42 | 6.5 | 0.01 | Dec 1, 2023 | A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. In order for an attacker to exploit the vulnerability, goose receiving blocks need to be configured. | ||
| CVE-2022-3353 | Med | 0.38 | 5.9 | 0.01 | Feb 21, 2023 | A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting… | ||
| CVE-2022-3864 | Med | 0.29 | 4.5 | 0.00 | Jan 4, 2024 | A vulnerability exists in the Relion update package signature validation. A tampered update package could cause the IED to restart. After restart the device is back to normal operation. An attacker could exploit the vulnerability by first gaining access to the system with… |
- risk 0.53cvss 8.1epss 0.01
Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during…
- risk 0.49cvss 7.5epss 0.02
Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of…
- risk 0.47cvss 7.2epss 0.02
Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to…
- risk 0.42cvss 6.5epss 0.01
A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. In order for an attacker to exploit the vulnerability, goose receiving blocks need to be configured.
- risk 0.38cvss 5.9epss 0.01
A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting…
- risk 0.29cvss 4.5epss 0.00
A vulnerability exists in the Relion update package signature validation. A tampered update package could cause the IED to restart. After restart the device is back to normal operation. An attacker could exploit the vulnerability by first gaining access to the system with…