VYPR
Medium severity6.4NVD Advisory· Published Dec 18, 2025· Updated Apr 15, 2026

CVE-2025-13911

CVE-2025-13911

Description

The vulnerability affects Ignition SCADA applications where Python scripting is utilized for automation purposes. The vulnerability arises from the absence of proper security controls that restrict which Python libraries can be imported and executed within the scripting environment. The core issue lies in the Ignition service account having system permissions beyond what an Ignition privileged user requires. When an authenticated administrator uploads a malicious project file containing Python scripts with bind shell capabilities, the application executes these scripts with the same privileges as the Ignition Gateway process, which typically runs with SYSTEM-level permissions on Windows. Alternative code execution patterns could lead to similar results.

AI Insight

LLM-synthesized narrative grounded in this CVE's description and references.

Affected products

1

Patches

Vulnerability mechanics

References

3

News mentions

0

No linked articles in our index yet.