VYPR
Unrated severityNVD Advisory· Published May 14, 2019· Updated Aug 4, 2024

CVE-2019-10918

CVE-2019-10918

Description

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

AI Insight

LLM-synthesized narrative grounded in this CVE's description and references.

Authenticated remote attacker via DCOM interface can execute arbitrary commands with SYSTEM privileges on Siemens SIMATIC products.

Vulnerability

A vulnerability exists in the DCOM interface of Siemens SIMATIC PCS 7, WinCC, and WinCC (TIA Portal) products. An authenticated attacker can exploit this to execute arbitrary commands with SYSTEM privileges. Affected versions include: SIMATIC PCS 7 V8.0 and earlier (all versions), V8.1 (all versions < V8.1 with WinCC V7.3 Upd 19), V8.2 (all versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), V9.0 (all versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11); SIMATIC WinCC (TIA Portal) V13 (all versions), V14 (all versions < V14 SP1 Upd 9), V15 (all versions < V15.1 Upd 3); SIMATIC WinCC Runtime Professional V13 (all versions), V14 (all versions < V14.1 Upd 8), V15 (all versions < V15.1 Upd 3); SIMATIC WinCC V7.2 and earlier (all versions), V7.3 (all versions < V7.3 Upd 19), V7.4 (all versions < V7.4 SP1 Upd 11), V7.5 (all versions < V7.5 Upd 3). [1]

Exploitation

An attacker with network access to the DCOM interface can exploit this vulnerability. The attacker must be authenticated with a low-privileged user account, and no user interaction is required. The exact steps involve sending crafted DCOM requests to the affected system. [1]

Impact

Successful exploitation allows the attacker to execute arbitrary commands with SYSTEM privileges, leading to full compromise of confidentiality, integrity, and availability of the affected system. [1]

Mitigation

Siemens has released updates to fix the vulnerability: for PCS 7 V8.1 (WinCC V7.3 Upd 19), V8.2 (WinCC V7.4 SP1 Upd 11), V9.0 (WinCC V7.4 SP1 Upd 11); WinCC (TIA Portal) V14 SP1 Upd 9, V15.1 Upd 3; WinCC Runtime Professional V14.1 Upd 8, V15.1 Upd 3; WinCC V7.3 Upd 19, V7.4 SP1 Upd 11, V7.5 Upd 3. Users should apply the appropriate updates. At the time of advisory publication, no public exploitation was known. [1]

AI Insight generated on May 26, 2026. Synthesized from this CVE's description and the cited reference URLs; citations are validated against the source bundle.

Affected products

17
  • Range: V7.2 and earlier all; V7.3 < V7.3 Upd19; V7.4 < V7.4 SP1 Upd11; V7.5 < V7.5 Upd3
  • Range: <= V8.0; V8.1 < V8.1 with WinCC V7.3 Upd19; V8.2 < V8.2 SP1 with WinCC V7.4 SP1 Upd11; V9.0 < V9.0 SP2 with WinCC V7.4 SP1 Upd11
  • Range: V13 all; V14 < V14 SP1 Upd9; V15 < V15.1 Upd3
  • Siemens AG/SIMATIC PCS 7 V8.0 and earlierv5
    Range: All versions
  • Siemens AG/SIMATIC PCS 7 V8.1v5
    Range: All versions < V8.1 with WinCC V7.3 Upd 19
  • Siemens AG/SIMATIC PCS 7 V8.2v5
    Range: All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11
  • Siemens AG/SIMATIC PCS 7 V9.0v5
    Range: All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11
  • Siemens AG/SIMATIC WinCC Runtime Professional V13v5
    Range: All versions
  • Siemens AG/SIMATIC WinCC Runtime Professional V14v5
    Range: All versions < V14.1 Upd 8
  • Siemens AG/SIMATIC WinCC Runtime Professional V15v5
    Range: All versions < V15.1 Upd 3
  • Siemens AG/SIMATIC WinCC (TIA Portal) V13v5
    Range: All versions
  • Siemens AG/SIMATIC WinCC (TIA Portal) V14v5
    Range: All versions < V14 SP1 Upd 9
  • Siemens AG/SIMATIC WinCC (TIA Portal) V15v5
    Range: All versions < V15.1 Upd 3
  • Siemens AG/SIMATIC WinCC V7.2 and earlierv5
    Range: All versions
  • Siemens AG/SIMATIC WinCC V7.3v5
    Range: All versions < V7.3 Upd 19
  • Siemens AG/SIMATIC WinCC V7.4v5
    Range: All versions < V7.4 SP1 Upd 11
  • Siemens AG/SIMATIC WinCC V7.5v5
    Range: All versions < V7.5 Upd 3

Patches

0

No patches discovered yet.

Vulnerability mechanics

AI mechanics synthesis has not run for this CVE yet.

References

2

News mentions

0

No linked articles in our index yet.