CVE-2019-10916
Description
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file. The vulnerability does impact the confidentiality, integrity, and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
AI Insight
LLM-synthesized narrative grounded in this CVE's description and references.
An SQL injection in Siemens SIMATIC PCS7, WinCC, and TIA Portal allows attackers with project file access to execute arbitrary system commands as the database server.
Vulnerability
An SQL injection vulnerability (CWE-89) exists in the project file handling of multiple Siemens SIMATIC products, including SIMATIC PCS 7, WinCC, and WinCC (TIA Portal) [1]. Affected versions include SIMATIC PCS 7 V8.0 and earlier (all versions), V8.1 prior to V8.1 with WinCC V7.3 Upd 19, V8.2 prior to V8.2 SP1 with WinCC V7.4 SP1 Upd 11, V9.0 prior to V9.0 SP2 with WinCC V7.4 SP1 Upd 11; SIMATIC WinCC (TIA Portal) V13 (all versions), V14 prior to V14 SP1 Upd 9, V15 prior to V15.1 Upd 3; SIMATIC WinCC Runtime Professional V13 (all versions), V14 prior to V14.1 Upd 8, V15 prior to V15.1 Upd 3; SIMATIC WinCC V7.2 and earlier (all versions), V7.3 prior to V7.3 Upd 19, V7.4 prior to V7.4 SP1 Upd 11, V7.5 prior to V7.5 Upd 3 [1]. The vulnerability allows an attacker with access to the project file to inject SQL commands.
Exploitation
An attacker with network access to the project file can exploit this vulnerability remotely with low skill level [1]. The attacker crafts a malicious project file containing an SQL injection payload. When the affected system processes the project file, the SQL injection is triggered, allowing the attacker to execute arbitrary system commands with the privileges of the local database server [1].
Impact
Successful exploitation enables arbitrary command execution on the database server, impacting the confidentiality, integrity, and availability of the affected system [1]. The attacker gains the privileges of the local database server, which could lead to full system compromise.
Mitigation
Siemens has released updates to address this vulnerability. Fixed versions include WinCC V7.3 Upd 19, WinCC V7.4 SP1 Upd 11, WinCC V7.5 Upd 3, TIA Portal V14 SP1 Upd 9, TIA Portal V15.1 Upd 3, WinCC Runtime Professional V14.1 Upd 8, WinCC Runtime Professional V15.1 Upd 3, and corresponding updates for PCS 7 [1]. Users should apply the latest updates. No workarounds are documented. At the time of advisory publication, no public exploitation was known [1].
AI Insight generated on May 26, 2026. Synthesized from this CVE's description and the cited reference URLs; citations are validated against the source bundle.
Affected products
17- Range: < V13, < V14.1 Upd8, < V15.1 Upd3
- Range: < V8.0 inclusive; < V8.1 Upd19; < V8.2 SP1 Upd11; < V9.0 SP2 Upd11
- Range: < V13, < V14 SP1 Upd9, < V15.1 Upd3
- Siemens AG/SIMATIC PCS 7 V8.0 and earlierv5Range: All versions
- Siemens AG/SIMATIC PCS 7 V8.1v5Range: All versions < V8.1 with WinCC V7.3 Upd 19
- Siemens AG/SIMATIC PCS 7 V8.2v5Range: All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11
- Siemens AG/SIMATIC PCS 7 V9.0v5Range: All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11
- Siemens AG/SIMATIC WinCC Runtime Professional V13v5Range: All versions
- Siemens AG/SIMATIC WinCC Runtime Professional V14v5Range: All versions < V14.1 Upd 8
- Siemens AG/SIMATIC WinCC Runtime Professional V15v5Range: All versions < V15.1 Upd 3
- Siemens AG/SIMATIC WinCC (TIA Portal) V13v5Range: All versions
- Siemens AG/SIMATIC WinCC (TIA Portal) V14v5Range: All versions < V14 SP1 Upd 9
- Siemens AG/SIMATIC WinCC (TIA Portal) V15v5Range: All versions < V15.1 Upd 3
- Siemens AG/SIMATIC WinCC V7.2 and earlierv5Range: All versions
- Siemens AG/SIMATIC WinCC V7.3v5Range: All versions < V7.3 Upd 19
- Siemens AG/SIMATIC WinCC V7.4v5Range: All versions < V7.4 SP1 Upd 11
- Siemens AG/SIMATIC WinCC V7.5v5Range: All versions < V7.5 Upd 3
Patches
0No patches discovered yet.
Vulnerability mechanics
AI mechanics synthesis has not run for this CVE yet.
References
2- cert-portal.siemens.com/productcert/pdf/ssa-697412.pdfmitrex_refsource_CONFIRM
- www.us-cert.gov/ics/advisories/ICSA-19-134-08mitrex_refsource_MISC
News mentions