Critical severity9.1NVD Advisory· Published Sep 12, 2018· Updated Jun 17, 2026
CVE-2018-13799
CVE-2018-13799
Description
A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. At the time of advisory publication no public exploitation of this vulnerability was known.
Affected products
2- Range: < V3.14-P021
- Siemens AG/SIMATIC WinCC OA V3.14 and priorv5Range: SIMATIC WinCC OA V3.14 and prior : All versions < V3.14-P021
Patches
Vulnerability mechanics
References
2- www.securityfocus.com/bid/105332nvdThird Party AdvisoryVDB Entry
- cert-portal.siemens.com/productcert/pdf/ssa-346256.pdfnvdVendor Advisory